Technical Parameters Of HZDPS Series
1.Voltage(Peak): 0-40kv, Sensitivity: 0.1kV, Accuracy: 1 %
2.Waveform: Ultra-low frequency sine wave, DC voltage, Voltage positive and negative peak error: ≤3%, Voltage waveform distortion: ≤1%
3.Frequency range:0.1 Hz 0.05 Hz 0.02 Hz, Load range(Ultra-low frequency test): 0nF–10μF
4.Current: Measurement range: 0–70 mA, Sensitivity: 1μA, Accuracy: 1 %
5.Tan Delta:
Ultra-low frequency sine wave voltage range: 1–40 kVrms
Load range: 50nF–5μF
Resolution: ≥1x10-6
Accuracy: ≥1x10-3
Measurement range: 1x10-3–21000x10-3
Tan Delta measurement frequency: 0.1Hz
Capacitance range: 50nF-5μF
Resistance value rang: 30MΩ-10GΩ
Dimensions: 48cm*28cm*58cm
Weight: 45kg
6.Working condition: indoor、outdoor; Temperature: -10℃~+40℃; Humidity:≤85%RH
7.Power supply: Frequency 50Hz,60hz, Voltage 100v -260V±5%.
8.USB communication port.
9.Power supply fuse pipe: see Table 3
10.Power supply: Voltage 220V±5%, 50±5Hz